Command Set
User command: %0118310610<CR>
Response: !18<CR>
Item Meaning Description
% (Leading Code) Command leading code.
01 (OldAddr) Original address ID is 01(Hex).
18 (NewAddr) New address ID is 18(Hex).
31 (OutputRange) Analog output range is 4 to 20 mA
06 (BaudRate) Baud rate is 9600.
10 (DataFormat) 10 means a slew rate is 1.000 mA/sec
and checksum is disable.
<CR> Carriage return 0x0D.
Code
(Hex)
Signal Range of Output Range Modules
30 0 to 20 mA 6021
31 4 to 20 mA 6021
32 0 to 10 V 6021
33 -10 to 10 V 6024
Table 0-1 Analog Output Range Setting
Code Baudrate
03 1200 bps
04 2400 bps
05 4800 bps
06 9600 bps
07 19200 bps
08 38400 bps
Table 3-2 Baud rate setting code