Command Set
35
3.11 4mA Offset Calibration
@Description
Stores the current output value as 4 mA reference at the specified analog
output module.(only 6021)
@Syntax
$(Addr)0<CR>
$
Command leading code
(Addr)
Address ID
0
Command Code
@Response
!(Addr)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid or no synchronized sampling
command was issued.
(Addr)
Address ID.
@Example
User command: $060<CR>
Response: !06<CR>
To perform the 4 mA calibartion for analog output module at address 06H.
Note : Analog output module should be trimmed to the correct value by “Trim
Calibration” command before to execute “4 mA Calibration”. Refers
to Chapter 5 “Analog Output Calibration” for details.